JZM1LE Series
Modular Case Residual Current Circuit Breaker

JZM1LE Series Cover

Introduction

JZM1LE Series Modular Case Residual Current Circuit Breaker (MRCB, also know as Modular Case Residual Current Device, MRCD) is suitable for circuits with a rated voltage of 400VAC (50Hz) and a rated current of 16A to 800A, in line with GB14048.2 and IEC60947-2 standards. JZM1LE series circuit breakers are mainly used to provide indirect contact protection for people who are at risk of electric shock, or to prevent electrical fires caused by contact with fault currents. It can also be used to protect circuits from overload and short-circuit. When other protection measures fail, JZM1LE series residual current circuit breaker with a rated residual operating current not exceeding 0.03A can be used as a supplementary protection for direct contact, but it cannot be used as the only direct contact protection. JZM1LE series circuit breakers have the advantages of small size, strong breaking capacity and short arcing distance. JZM1LE series circuit breakers can be equipped with alarm contacts, shunt releases, undervoltage releases, auxiliary contacts, rotary handle operating mechanisms, electric operating mechanisms and other accessories. JZM1LE series circuit breakers have multiple wiring methods such as front wiring, rear wiring and plug-in wiring. JZM1LE series circuit breakers can be installed vertically and horizontally.


How to order

JZM1LE Series How to order 1


The neutral pole (N pole) type of the four-pole (4P) circuit breaker:

Type A: N pole is not installed with an overcurrent release, and N pole is always connected, and it is not working together with other three poles;

Type B: N pole is not installed with overcurrent release, and it is working together with other three poles (N pole is closed first and then opened);

Type C: N pole is installed with an overcurrent release, and it is working together with other three poles (N pole is opened first and then closed);

Type D: N pole is installed with an overcurrent release, and the N pole is always connected, and it is not working together with other three poles.


Accessory Model Table:

JZM1LE Series How to order 2

Note: Alarm contact●; Shunt release■; Auxiliary contact○; Undervoltage release▲; The model with Y in brackets (such as 210Y) means the shunt release with delay function, the action delay time is 0.5s~2s, and the control voltage is 240VAC/400VAC.


Application environment

● Ambient temperature: -5℃~+40℃, the average value of 24h does not exceed +35℃. If the circuit breaker works in an environment where the temperature is higher than +40°C or lower than -5°C, please contact us;

● Altitude: ≤2000m;

● Relative humidity: monthly average ≤90% (the average temperature of the month is +25℃); relative humidity ≤50% (when the ambient temperature is +40℃). The relative humidity is related to the ambient temperature. The lower the ambient temperature, the higher the allowable relative humidity. For condensation caused by temperature changes, take appropriate protective measures (such as adding drainage holes);

● Air pollution level: Level Ⅲ;

● Installation category: Class Ⅲ;

● Installation site: no significant shaking, impact and vibration, and the external magnetic field of the installation site should not exceed 5 times the geomagnetic field in any direction.


Application example

JZM1LE Series Application example


Level Ⅰ Protection,

Cross-sectional area of copper core plastic insulated wire: 50mm2

Rated working current: 250A

Rated residual operating current: 300mA~500mA

Residual current breaking time: 0.6s≤t≤0.8s

Suggested residual current circuit breaker: JZM1LE-250, JZM1LE-400


Level Ⅱ Protection,

Cross-sectional area of copper core plastic insulated wire: 4~16mm2

Rated working current: 40A, 63A, 80A, 100A,

Rated residual operating current: 100mA~300mA

Residual current breaking time: 0.25s≤t≤0.4s

Suggested residual current circuit breaker: JZM1LE-125, JZM1LE-250


Level Ⅲ Protection,

Cross-sectional area of copper core plastic insulated wire: 1.5~4mm2

Rated working current: 20A, 32A, 40A

Rated residual operating current: 30mA or more smaller

Residual current breaking time: t≤0.1s or more faster

Suggested residual current circuit breaker: JZM1LE-125


Level Ⅳ Protection,

Cross-sectional area of copper core plastic insulated wire: 1~2.5mm2

Rated working current: 20A, 32A

Rated residual operating current: 10mA or more smaller

Residual current breaking time: Fast action type

Suggested residual current circuit breaker: JZM1LE-125, JZB1LE-125


Technical data-sheet

Table 1: main parameters of residual current operated circuit breaker

JZM1LE Technical data-sheet 1


Table 2: action characteristics of overcurrent release of residual current circuit breaker

1. Thermal electromagnetic overcurrent release

The following is the inverse time breaking characteristic of the thermal electromagnetic overcurrent release of the residual current circuit breaker when all poles are energized at the same time:

1.1 For power distribution

JZM1LE Technical data-sheet 2

1.2 For motor protection

JZM1LE Technical data-sheet 3

Note: 16A~40A residual current circuit breaker has no motor protection function


2. Electromagnetic overcurrent release

The following is the inverse time breaking characteristic of the electromagnetic overcurrent release of the residual current circuit breaker when all poles are energized at the same time:

2.1 For power distribution: the instantaneous action characteristic is set to 10In (±20%).

2.2 For motor protection: the instantaneous action characteristic is set to 12In (±20%).


Table 3: residual current protection action time of residual current circuit breaker

3.1 Non-time-delay type

The action characteristics of the non-time-delay type residual current circuit breaker are as follows:

JZM1LE The action characteristics of the non-time-delay type residual current circuit breaker

Note: 1) For circuit breakers with lΔn≤30mA, 5lΔn can be replaced by 0.25A. 2) If 5IΔn replayced by 0.25A, then 10lΔn is 0.5A.


3.2 Time-delay type

The limit non-driving time of the time-delay type residual current circuit breaker is specified by 2lΔn, and its action characteristics are as follows:

JZM1LE Time-delay type


Table 4: inverse time protection characteristic curve of residual current circuit breaker

JZM1LE inverse time protection characteristic curve of residual current circuit breaker


Appearance and mounting dimensions

JZM1LE Series Appearance and mounting dimensions 1


JZM1LE Series Appearance and mounting dimensions 2